Calculator 05 · Backup power
How many generators, how much diesel?
Pick the outage load, generator size, redundancy and runtime. See the generator yard, the fuel to store and the tanker loads to refill it.
Share of facility load the generators must carry.
Generator size
Redundancy
Check the generator spec sheet; this starts at an example value.
Carrying loadRedundant
Generators
21
20 to carry 60 MW, plus 1 for redundancy
Installed capacity
63.0MW
Each truck = one tanker load · 48 hours at load
Diesel stored
201,600gal
Burn at load
4,200gal/hr
Tanker loads to refill
26
For early planning only. Results follow from the inputs and the stated assumptions; they are not engineering, financial or legal advice.
How the math works
Generators to carry the load
Fuel = load × burn rate × hours
Refilling the tanks
Questions
How many generators does a 60 MW data center need?
With 3 MW generators carrying the full load, 60 MW needs 20 units, plus one spare at N+1 for 21. At 2N it would be 40.
What is N+1 versus 2N?
N is the number of generators needed to carry the load. N+1 adds one spare so any single unit can fail; 2N doubles the whole set so an entire system can fail or be taken out of service.
How much diesel is typical to store?
Designs commonly hold enough fuel for one to several days at load. The right runtime depends on the reliability target, the local fuel supply and permit limits on storage and runtime.
Do generators need air permits?
Usually. Large diesel generator fleets are regulated sources of air emissions, and permits can cap their annual runtime. See the guide on air permits for data center generators.